Emergency lighting e856 series

Characteristics

Type
emergency lighting
Illumination technology
LED
Applications
for workstations
Other characteristics
polycarbonate, for hazardous locations
Power

6 W, 11 W, 19 W

Description

Small LED-Emergency Light Fitting for Ex-Zone 1/21
Series e856 …

Applications:
Hazardous areas in Zones 1/2 (gas) and 21/22 (dust) as safety illumination e.g. for workstations with special hazard , i.e. as information or escape route lighting with pictogram for identification of escape routes.

Mechanical design:
Housing: Glass fibre reinforced polyester resin. Version H with separate battery box at one small side of the housing.
Diffuser: Clear polycarbonate, frosted, detachable, silicone gasket.
Reflector: white, detachable, carrying the encapsulated LED-modules and protection cover.
Central locking system: Operated by a hexagonal box spanner 13mm.
Connection: Prepared for looping the mains cable at one end 4 x 2.5mm². Terminal L1 + L1’ + N + PE, up to 2.5 mm².
Cable entries: 2 entries M25 x 1.5 at the front side of the light fitting (2 cable glands, 1 with blanking plug).
Mounting: Side fixing brackets allow direct mounting on to walls or ceilings (Version without battery box). Mounting accessories see spare parts/ accessories.

Technical Data:

LED: Line modules ca. 6,500K, CRI > 80,, Lifetime L70B10 > 80.000h,
L80B50 > 80.000h at max. ambient temperature
ECG with emergency light electronic
Incorporated NiCd battery, electronic charger, short circuit protected battery and
reverse battery protection
Electronic deep discharge protection: acc. to EN 61347-2-7
Re-charging time: 24h, acc. to EN 60598-2-22
Automatic monitoring: of the emergency light fitting according to EN 62034, indication of the test results by 2-coloured LED (luminescence diode) at the luminaire